| Voltage Monitoring Relay | For 1P2W or 3P4W Network |
| According Standard | IEC60255-25 EN61000-4-2/3/4/5 |
| Supply | Self Power |
| Input | 0 - 500VAC L-L |
| Frequency | 50/60Hz ±10% |
| Voltage threshold | Under: 0.7 - 0.95xU Over : 1.05 - 1.3xU |
| Phase-Phase un-balance | 15% Fix |
| Delay time | 0.1 - 25 sec. |
| Instant tripping time | <1sec. |
| Reset time | 1 - 6sec. |
| Repeat accuracy | Better than ±1% |
| Hysteresis | 3V |
| Output | 1 C/O |
| Operation temperature | -20 - +50C |
| Humidity | <95% no condensation |
|
Model |
Features |
Technical data |
|
MUR-02 |
Voltage Over & Under |
2P2W L-N:150-300VAC 50/60Hz |
|
Setting range: 70~95%(under); 105~130%(over)(Self-power) |
||
|
MUR-04 |
Phase fault |
3P4W L-N:150-300VAC 50/60Hz |
|
Voltage Over & Under |
Setting range: 70~95%(under); 105~130%(over)(Self-power) |
|
|
MUR-04F |
Phase fault, phase sequence, voltage unbalance |
3P4W L-N:150-300VAC 50/60Hz |
|
Voltage Over & Under |
Setting range: 70~95%(under); 105~130%(over)(Self-power) Fixed voltage unbalance: 15% |
|
|
MUR-04D |
Phase fault |
3P4W L-N:150-300VAC 50/60Hz |
|
Voltage Over & Under |
Setting range: 70~95%(under); 105~130%(over) |