Voltage Monitoring Relay | For 1P2W or 3P4W Network |
According Standard | IEC60255-25 EN61000-4-2/3/4/5 |
Supply | Self Power |
Input | 0 - 500VAC L-L |
Frequency | 50/60Hz ±10% |
Voltage threshold | Under: 0.7 - 0.95xU Over : 1.05 - 1.3xU |
Phase-Phase un-balance | 15% Fix |
Delay time | 0.1 - 25 sec. |
Instant tripping time | <1sec. |
Reset time | 1 - 6sec. |
Repeat accuracy | Better than ±1% |
Hysteresis | 3V |
Output | 1 C/O |
Operation temperature | -20 - +50C |
Humidity | <95% no condensation |
Model |
Features |
Technical data |
MUR-02 |
Voltage Over & Under |
2P2W L-N:150-300VAC 50/60Hz |
Setting range: 70~95%(under); 105~130%(over)(Self-power) |
||
MUR-04 |
Phase fault |
3P4W L-N:150-300VAC 50/60Hz |
Voltage Over & Under |
Setting range: 70~95%(under); 105~130%(over)(Self-power) |
|
MUR-04F |
Phase fault, phase sequence, voltage unbalance |
3P4W L-N:150-300VAC 50/60Hz |
Voltage Over & Under |
Setting range: 70~95%(under); 105~130%(over)(Self-power) Fixed voltage unbalance: 15% |
|
MUR-04D |
Phase fault |
3P4W L-N:150-300VAC 50/60Hz |
Voltage Over & Under |
Setting range: 70~95%(under); 105~130%(over) |