Characteristics
|
RPM80
|
|
Auxiliary supply
|
||
Operating voltage (Un)
|
85···265 VAC 50/24-48VDC,4VA(Depend on order)
|
|
Power consumption
|
4VA
|
|
Frequency
|
45···65Hz
|
|
Voltage measurement input
|
||
Measurement range
|
10···690VAC L-L
|
|
Measuring mode
|
True RMS
|
|
Measuring input impedance
|
4MΩ
|
|
Method of connection
|
single-phase,two-phase,three-phase
|
|
Current measurement input
|
||
Reference current
|
1A or 5A
|
|
Measuring range
|
0,05···5.5A
|
|
Measuring mode
|
True RMS
|
|
Overload capacity
|
10A (Through the external current transformer)
|
|
Self-consumption
|
0,2VA
|
|
Accuracy
|
||
Measures |
Voltage
|
± 0,2% according to IEC61557-12
|
Current
|
± 0,2% according to IEC61557-12
|
|
Power
|
± 0,5%
|
|
Power factor
|
± 0,5%
|
|
Harmonics
|
± 1%
|
|
Frequency
|
± 0,02%
|
|
Active Energy ±
|
CL 0.5S according to IEC62053-22
|
|
Reactive Energy ±
|
CL 0.5S according to IEC62053-22
|
|
Insulation
|
||
Insulation voltage
|
3kV for 1min,50Hz
|
|
Display
|
||
Display type 240x160 pix LCD
|
Ambient condition
|
|||
Opterating temperature
|
-10···+55°C
|
||
Storage temperature
|
-25···+75°C
|
||
Housing
|
|||
|
|
Flush mount 96*96mm
|
|
Size
|
The panel cut-size 92*92mm
|
||
Degree of protection |
|
IP40(optional IP54) on front
|
|
|
IP20 housing and terminals
|
||
Weight
|
400g
|
||
Standard
|
|||
Reference standard |
EN61010.1; EN60529; EN62053-21; EN62053-23;
N61000-4-2; EN61000-4-3; EN61000-4-4; EN61000-4-5; EN61000-4-6;EN61000-4-8; EN61000-4-11;EN61000-3-2 |
||
►Measuring: VL-L, VL-N, I, In, Cos, Pf, Hz, W, ΣW, Va, ΣVa,Var, ΣVar, Kwh, Kvarh, THD-U, THD-I, 1-63th harmonics
►Real time clock ►System running hours ►1-24 months energy calculate and recording ►7 digital input and 2 relay output(remote or alarm) or analog output ►Waveforms and phase diagram for voltage, current ►Waveform record and sag, swell and transient event capture. ►Alarm event Log(over and under): VL-L, VL-N, I, In, ΣW, ΣVar,THD-U, THD-I ►RS485 communication (MODBUS RTU) |