Multimeter/Network Analyzer

RPM60m digital multifunction power analyser-class S

RPM60m digital multifunction power analyser-class S
Description
►True RMS measurements (512 samples/cycle)
►For single-phase, two-phase, three-phase system
►Measurements:VL-L, VL-N, I, In, Cos∅, Pf, Hz, W, ∑W, Va, ∑Va, Var, 
    ∑Var, import Kwh, export Kwh  import Kvarh, export Kvarh, V-THD, I-THD,
    1-63th harmonic , system running hours, % voltage unbalance, 
    % current unbalance, % system load, total frequency, temperature & humidity(option)
►3 voltage and 4 current input (Measure or calculate the neutral current)
►Maximum, minimum and demand for U, I, P, Q, S in hours, days, months
►Voltage Input: 0-690Vac, Current input: 1 or 5A CT selective
►% system load and system running hours
►Real time clock with integrated backup rechargeable battery
►Four quadrants energy measurement and Monthly energy calculation
►2 pulse output  and  RS485 communication: Modbus RTU
►USB port (Type C) for data transfer
►Built in 64Mbit flash memory for datalog
►Data recorded in standard excel file formats for further En50160 analysis
►Comply BEC2018 in clause7.7.1-7.7.3 store data:
     [Voltage(L-L, L-N), Current(3P and neutral), total power factor, total energy consumption(Kwh), maximum demand(kVA),
     total harmonic distortion for 3phase voltage and current] at least 3years in interval of 15 minutes
► English, Chinese (traditional & simplied) or Other language
► Moduel function options (only one can be selected)
     ● 7 digital input +2 relay output(remote or alarm)(Standard)
     ● 7 digital input +2 analog output(4-20mA) for V1,V2,V3,V12,V23,V31,I1,I2,I3 (option)
     ● Ethernet (Modbus TCP), Web server+2 digital input +2 relay output(remote or alarm) (option)
     ● Temperature & humidity Measurement +2 digital input +2 relay output(remote or alarm) (option)
 
Characteristics
RPM60
Auxiliary supply
Operating voltage (Un)
85···265 VAC 50/24-48VDC,4VA(Depend on order)
Power consumption
4VA
Frequency
45···65Hz
Voltage measurement input
Measurement range
10···690VAC L-L
Measuring mode
True RMS
Measuring input impedance
4MΩ
Method of connection
single-phase,two-phase,three-phase
Current measurement input
Reference current
1A or 5A
Measuring range
0,05···5.5A
Measuring mode
True RMS
Overload capacity
10A (Through the external current transformer)
Self-consumption
0,2VA
Accuracy
 
 
Measures
Voltage
± 0,2% according to IEC61557-12
Current
± 0,2% according to IEC61557-12
Power
± 0,5%
Power factor
± 0,5%
Harmonics
± 1%
Frequency
± 0,02%
Active Energy ±
CL 0.5S according to IEC62053-22
Reactive Energy ±
CL 0.5S according to IEC62053-22
Insulation
Insulation voltage
3kV for 1min,50Hz
Display
Display type                                                   240x160 pix LCD
Ambient condition
Opterating temperature
-10···+55°C
Storage temperature
-25···+75°C
Housing
 
 
Flush mount 96*96mm
 
Size                                                
The panel cut-size 92*92mm
 
Degree of protection
 
IP40(optional IP54) on front
 
IP20 housing and terminals
Weight
400g
Standard
  
Reference standard
IEC61010-1; IEC61557-1;
IEC61557-12; IEC61326-1;
IEC62053-21; IEC62053-22; 
IEC62053-31; IEC60068-2-1; 
IEC60068-2-30; IEC60364-5-52; 
IEC61000-3-2; IEC61000-3-3;
IEC61000-4-2; IEC61000-4-3;
IEC61000-4-4; IEC61000-4-5;
IEC61000-4-6; IEC61000-4-8;
IEC61000-4-11; IEC61000-4-30
►Measuring: VL-L, VL-N, I, In, Cos, Pf, Hz, W, ΣW, Va, ΣVa,Var, ΣVar, 
                        Kwh, Kvarh, THD-U, THD-I, 1-63th harmonics 
►Real time clock
►System running hours
►2 or 7 digital input and 2 relay output(remote or alarm) or analog output
►USB and RS485 communication: Modbus RTU
►Ethernet communication: Modbus TCP, Web server (depend on order)